Voltage Drop & Length

Voltage drop and loop impedance along a feeder from the transformer through main and sub-distribution to the load, with the remaining budget, maximum cable length and smallest suitable cross-section for every section

Sample values, replace with your own feeder data
Voltage drop along the feeder
Hover over the chart to read the values
Voltage drop Transformer Permitted voltage drop Loop impedance Zs Zs,max of the protective device
Supply
Limits & calculation
Feeder sections · from the origin to the load
#SectionSystemIb Acos φLength mCross-sectionConductorParallelProtective deviceIn A
Each section carries the current of everything downstream. Single-phase sections are rated against U0. The protective conductor is taken equal to the line conductor.

Supply

Feeder total

Reference limits

Assessment

    Sections

    #SectionCableR′ Ω/kmX′ Ω/kmΔU VΔU %Σ ΔU %Zs ΩZs,max ΩMax. length ΔU mMax. length Zs mMin. cross-sectionStatus

    Method: voltage drop per section ΔU = k × Ib × L × (R′ cos φ + X′ sin φ) / n with k = √3 for three-phase and 2 for single-phase sections and n parallel cables; percentages refer to U (three-phase) or U0 (single-phase) and are added along the feeder. R′ from the conductor resistance of IEC 60228 at the selected conductor temperature with skin and proximity effect, X′ from the conductor spacing of a multi-core cable. Transformer: Z = uk × U² / Sr, R = Pk × U² / Sr², voltage drop at the load ΔU = S / Sr × (uR cos φ + uX sin φ), short-circuit current Ik3 = c × U / (√3 × Z) with c = 1.05; the medium-voltage network is neglected. Loop impedance Zs = Zs at the origin plus 2 × L × |Z′| / n per section, added as magnitudes (on the safe side), at a conductor temperature of at least 70 °C. Disconnection per VDE 0100-410: Zs ≤ 0.95 × U0 / Ia with Ia = 5 / 10 / 20 × In for MCB B / C / D, typical values of gG fuses and Ii = 10 × Ir for circuit breakers. Maximum length and smallest cross-section of a section keep all other sections unchanged; for disconnection every downstream protective device is checked as well. Reference limits: VDE 0100-520 Annex G (3 % lighting / 5 % other uses from a public LV supply, 6 % / 8 % from an own transformer), DIN 18015-1 (3 % from the meter in residential buildings). Current-carrying capacity is not checked here; use Cable Sizing. Disclaimer: this tool is a planning aid. Results are not a substitute for design by a qualified electrical engineer and must be checked against the applicable standards (DIN VDE 0100-410, -520, DIN 18015-1, technical connection conditions of the network operator) and the manufacturer data before installation. oxinon.com accepts no liability for damage resulting from the use of these results.

    Free demo with 6 of 24 tools. Full version at oxinon.com ›