Air Volume & Ventilation

Outdoor air per EN 16798-1 from persons and building emissions or from the CO₂ limit, supply air for the sensible cooling load, air change and CO₂ in the room, room by room with totals for the air handling unit

Sample values, replace with your own rooms
Outdoor air and supply air by room
Hover over the chart to read the values
Outdoor air Supply air for cooling Recirculating units CO₂ per room Limit of the category Occupied Persons Building emissions By CO₂ limit
Rooms
#RoomUseArea m²Height mPersonsCooling load WΔt K
Empty fields use the typical values of the use (grey): occupancy per EN 16798-1, sensible cooling load from internal and solar gains plus the persons, supply air temperature difference. Enter the cooling load from your VDI 2078 calculation where it is available.
Indoor air quality
Cooling & air handling unit

Outdoor air

Supply air & cooling

Air handling unit

Assessment

    Rooms

    RoomPersonsPersons m³/hBuilding m³/hBy CO₂ m³/hOutdoor air m³/hl/s per personCooling load WFor cooling m³/hSupply air m³/hAir change 1/hCO₂ ppm

    Method: outdoor air per EN 16798-1 Annex B, method 1: q = n × qp + A × qB with qp = 10 / 7 / 4 / 2.5 l/s per person and qB = 0.5 / 0.35 / 0.2 / 0.15 (very low-polluting), 1.0 / 0.7 / 0.4 / 0.3 (low-polluting) or 2.0 / 1.4 / 0.8 / 0.6 l/(s·m²) (not low-polluting) for categories I / II / III / IV, divided by the ventilation effectiveness εv. Method 2 (CO₂ limit): q = n × G / ΔC with a CO₂ emission G = 17 l/h per person and met (adult) and ΔC = 550 / 800 / 1350 / 1350 ppm above outdoor air, but not less than the building component A × qB. Occupancy from the floor area per person of EN 16798-1 / EN 15251 (single office 10, open-plan office 15, meeting room 2, classroom 2, auditorium 0.75, restaurant 1.5, retail 7 m² per person) unless entered. CO₂ in the room: steady state C = Cout + n × G / (q × εv), course over time with C(t) = Css + (C0 − Css) × e^(−q t / V) for the occupied hours and the decay afterwards. Supply air for the sensible cooling load V = Q / (ρ × cp × Δt) with ρ × cp = 0.335 Wh/(m³·K); all-air system: supply air = higher of outdoor air and cooling air, the difference is recirculated; outdoor air + room units: supply air = outdoor air, room units cover the rest of the load. IT and technical rooms are cooled by recirculating units; the air handling unit supplies only their outdoor air. AHU cross-section = design air flow × diversity / face velocity, velocity class per EN 13053. Disclaimer: this tool is a planning aid. Results are not a substitute for design by a qualified engineer and must be checked against the applicable standards and regulations (EN 16798-1, EN 16798-3, DIN 1946-4 for health care, workplace rules ASR A3.6, VDI 2078 for the cooling load) before construction. oxinon.com accepts no liability for damage resulting from the use of these results.